| CONDUCTOR | Stranded Annealed Copper Conductor (IEC 60228-Class 2) | ||
| INSULATION | PE | EN 50290-2-23 | |
| INDIVIDUAL SCREEN | PES and ALPES Tape with Tinned Copper Wire (0,50 mm²) | ||
| OVERALL SCREEN | PES and ALPES Tape with Tinned Copper Wire (0,50 mm²) | ||
| SHEATH | PVC Compound | Black | EN 50290-2-22 |
| PHYSICAL&ELECTRICAL CHARACTERISTICS | |
| MAX. CONDUCTOR TEMPERATURE DURING SHORT CIRCUIT | 160°C |
| NOMINAL VOLTAGE | 300 V |
| TEST VOLTAGE | 1500 V |
| OPERATING TEMPERATURE | -30°C … +70°C |
| MINUMUM BENDING RADIUS | 10 X D |
| FIRE PERFORMANCE CHARACTERISTICS | |
| FLAME RETARDANT | IEC 60332-1 |
| NO FLAME PROPAGATION | IEC 60332-3-24 |
| OTHER CHARACTERISTICS | |
| UV RESISTANCE | ISO 4892-2 / ISO 4892-3 |
| WATER RESISTANCE | AD7 |
| Number of Core and Cross Section Area (mm²) | Max. Mutual Capacitance (pF/m) | Max. L/R (Ratio) (μH/km) | Approx. Overall Diameter (mm) (±10%) | Approx. Cable Weight (kg/km) | Max. Conductor Resistance DC at 20ºC (Ohm/km) |
| 12 x 2 x 1,3 rm | 150 | 40 | 21,10 | 596 | 14,2 |
| 24 x 2 x 1,3 rm | 150 | 40 | 29,80 | 1154 | 14,2 |