| CONDUCTOR | Solid Annealed Copper Conductor (IEC 60288-Class 1) |
| INSULATION | XLPE |
| BEDDING | Thermoplastic Filler |
| INNER SHEATH | PVC Compound |
| DRAIN WIRE | Tinned Copper Wires |
| BRAID | Galvanised Steel Wire Braid |
| SHEATH | PVC Compound |
| PHYSICAL&ELECTRICAL CHARACTERISTICS | |
| MAX. CONDUCTOR TEMPERATURE DURING SHORT CIRCUIT | 250°C |
| NOMINAL VOLTAGE | 600/1000 V |
| TEST VOLTAGE | 3500 V |
| OPERATING TEMPERATURE | -40°C … +90°C |
| MINUMUM BENDING RADIUS | 12 X D |
| FIRE PERFORMANCE CHARACTERISTICS | |
| FLAME RETARDANT | IEC 60332-1 |
| NO FLAME PROPAGATION | IEC 60332-3-24 |
| OTHER CHARACTERISTICS | |
| UV RESISTANCE | ISO 4892-2 / ISO 4892-3 |
| WATER RESISTANCE | AD7 |
| OIL RESISTANCE | ASTM NO: 2 (4 hours 70°C) |
| HYDROCARCON RESISTANCE | NF-M87-202 |
| Number of Core and Cross Section Area (mm²) | Approx. Overall Diameter (mm) (±5%) | Approx. Cable Weight (kg/km) | Max. Conductor Resistance DC at 20ºC (Ohm/km) |
| 4 x 4 re | 17,40 | 412 | 4,61 |
| 4 x 6 rm | 18,60 | 508 | 3,08 |
We use cookies on our website to provide you with a better experience. For further information, please refer to our Cookie Policy
and Privacy Notice.