H07V-R

Certificates

CONDUCTOR Stranded Annealed Copper Conductor (IEC 60228-Class 2)
INSULATION PVC Compound - TI1 (EN 50363-3)
PHYSICAL&ELECTRICAL CHARACTERISTICS
MAX. CONDUCTOR TEMPERATURE DURING SHORT CIRCUIT 160°C
NOMINAL VOLTAGE 450/750 V
TEST VOLTAGE 2000 V
OPERATING TEMPERATURE -30°C … +70°C
MINUMUM BENDING RADIUS 12 X D
FIRE PERFORMANCE CHARACTERISTICS
FLAME RETARDANT IEC 60332-1
OTHER CHARACTERISTICS
UV RESISTANCE ISO 4892-2 / ISO 4892-3
WATER RESISTANCE AD7
Number of Core and Cross Section Area (mm²) Approx. Overall Diameter (mm) (±5%) Approx. Cable Weight (kg/km) Max. Conductor Resistance DC at 20ºC (Ohm/km)
1 x 120 16,4 1161 0,153
1 x 150 18,2 1436 0,124
1 x 300 26,1 2926 0,0601
1 x 500 34 4798 0,0366