Home » Control Cables » LI2YCY

LI2YCY

Certificates

CONDUCTOR Stranded Annealed Copper Conductor (IEC 60228-Class 2)
INSULATION PE JZ-OZ-DIN 47100
SEPERATOR Polyester Tape
BRAID Tinned Copper Wire Braid 85% Coverage
SHEATH LSZH Compound Grey
PHYSICAL&ELECTRICAL CHARACTERISTICS
MAX. CONDUCTOR TEMPERATURE DURING SHORT CIRCUIT 160°C
NOMINAL VOLTAGE 300/500 V
TEST VOLTAGE 2000 V
OPERATING TEMPERATURE -30°C … +70°C
MINUMUM BENDING RADIUS 10 X D
FIRE PERFORMANCE CHARACTERISTICS
FLAME RETARDANT IEC 60332-1
OTHER CHARACTERISTICS
UV RESISTANCE ISO 4892-2 / ISO 4892-3
WATER RESISTANCE AD7
Number of Core and Cross Section Area (mm²) Approx. Overall Diameter (mm) (±5%) Approx. Cable Weight (kg/km) Max. Conductor Resistance DC at 20ºC (Ohm/km)
4 x 2 x 0,5 rm 10,90 155 36
8 x 2 x 0,5 rm 13,60 243 36