| CONDUCTOR | Stranded Annealed Copper Conductor (IEC 60288-Class 2) | ||
| INSULATION | PVC Compound | HD 308 S2 | PVC/A (IEC 60502-1) |
| BEDDING | PVC Compound | ||
| ARMOUR | ARMOUR Galvanised Steel Wire (Aluminium Wire for Single Core) | ||
| SHEATH | PVC Compound | Black | ST1 (IEC 60502-1) |
| PHYSICAL&ELECTRICAL CHARACTERISTICS | |
| MAX. CONDUCTOR TEMPERATURE DURING SHORT CIRCUIT | 160°C |
| NOMINAL VOLTAGE | 600/1000 V |
| TEST VOLTAGE | 3500 V |
| OPERATING TEMPERATURE | -30°C … +70°C |
| MINUMUM BENDING RADIUS | 12 X D |
| FIRE PERFORMANCE CHARACTERISTICS | |
| FLAME RETARDANT | IEC 60332-1 |
| OTHER CHARACTERISTICS | |
| UV RESISTANCE | ISO 4892-2 / ISO 4892-3 |
| Number of Core and Cross Section Area (mm²) | Approx. Overall Diameter (mm) (±5%) | Approx. Cable Weight (kg/km) | Max. Conductor Resistance DC at 20ºC (Ohm/km) |
| 12 x 16 rm | 20.80 | 1004 | 1.15 |
| 4 x 16 rm | 24.30 | 1530 | 1.15 |
| 4 x 35 rm | 31.10 | 2672 | 0.524 |
| 4 x 50 rm | 37.10 | 3731 | 0.387 |
| 4 x 70 rm | 41.40 | 4845 | 0.268 |
| 4 x 95 rm | 47.70 | 6760 | 0.193 |
| 4 x 150 rm | 56.70 | 9722 | 0.124 |