| CONDUCTOR | Stranded Tinned Copper Conductor (IEC 60288-Class 2) | ||
| INSULATION | XLPE | EN 50290-2-29 | |
| FIRE RESISTANT TAPE | PES and ALPES Tape with Tinned Copper Wire (0,50 mm²) | ||
| BRAID | PES and ALPES Tape with Tinned Copper Wire (0,50 mm²) | ||
| BEDDING | LSZH Compound | ||
| BRAID | Galvanised Steel Wire Braid | 82% Coverage | |
| SHEATH | LSZH Compound | Black | EN 50290-2-27 |
| PHYSICAL&ELECTRICAL CHARACTERISTICS | |
| MAX. CONDUCTOR TEMPERATURE DURING SHORT CIRCUIT | 250°C |
| NOMINAL VOLTAGE | 500 V |
| TEST VOLTAGE | 2000 V |
| OPERATING TEMPERATURE | -40°C … +90°C |
| MINUMUM BENDING RADIUS | 12 X D |
| FIRE PERFORMANCE CHARACTERISTICS | |
| FLAME RETARDANT | IEC 60332-1 |
| NO FLAME PROPAGATION | IEC 60332-3-24 |
| HALOGEN-FREE | IEC 60754-1, VDE 0482 P267-2-1, DIN EN50267-2-1 |
| NO CORROSIVE GASES | IEC 60754-2, VDE 0482 P267-2-2, DIN EN 50267-2-2 |
| LOW SMOKE EMISSION | IEC 61034-1/-2, VDE 0482 P268-1/-2, DIN EN 50268-1/-2 |
| OTHER CHARACTERISTICS | |
| UV RESISTANCE | ISO 4892-2 / ISO 4892-3 |
| WATER RESISTANCE | AD7 |
| OIL RESISTANCE | ASTM NO: 2 (4 hours 70°C) |
| HYDROCARCON RESISTANCE | NF-M87-202 (Aliphatic Hydrocarbon) |
| Number of Core and Cross Section Area (mm²) | Max. Mutual Capacitance (pF/m) | Max. L/R (Ratio) (μH/km) | Approx. Overall Diameter (mm) (±10%) | Approx. Cable Weight (kg/km) | Max. Conductor Resistance DC at 20ºC (Ohm/km) |
| 5 x 2 x 1,5 rm | 150 | 40 | 20,10 | 573 | 12,2 |
| 10 x 2 x 1,5 rm | 150 | 40 | 27,20 | 954 | 12,2 |
| 20 x 2 x 1,5 rm | 150 | 40 | 34,50 | 1595 | 12,2 |