P1 T2 OSCR

Certificates

CONDUCTOR Solid Annealed Copper Conductor (IEC 60228-Class 1)
INSULATION PE EN 50290-2-23
OVERALL SCREEN PES and ALPES Tape with Tinned Copper Wire (0,50 mm²)
BEDDING PE
ARMOUR Galvanised Steel Wire (Aluminium Wire for Single Core)
SHEATH PVC Compound Black or Blue EN 50290-2-22
PHYSICAL&ELECTRICAL CHARACTERISTICS
MAX. CONDUCTOR TEMPERATURE DURING SHORT CIRCUIT 160°C
NOMINAL VOLTAGE 300/500 V
TEST VOLTAGE 2000 V
OPERATING TEMPERATURE -30°C … +70°C
MINUMUM BENDING RADIUS 12 X D
FIRE PERFORMANCE CHARACTERISTICS
FLAME RETARDANT IEC 60332-1
OTHER CHARACTERISTICS
UV RESISTANCE ISO 4892-2 / ISO 4892-3
WATER RESISTANCE AD7
Number of Core and Cross Section Area (mm²) Max. Mutual Capacitance (pF/m) Max. L/R (Ratio) (μH/km) Approx. Overall Diameter (mm) (±10%) Approx. Cable Weight (kg/km) Max. Conductor Resistance DC at 20ºC (Ohm/km)
1 x 2 x 1 re 115 25 10.00 202 18.1
1 x 4 x 1 re 75 25 11.20 252 18.1
5 x 2 x 1 re 75 25 17.10 545 18.1
10 x 2 x 1 re 75 25 22.60 843 18.1
20 x 2 x 1 re 75 25 29.00 1444 18.1

We use cookies on our website to provide you with a better experience. For further information, please refer to our Cookie Policy