JE-H(St)H...Bd

Generally used in; telephone, measurement and control systems. These cables have low smoke emission and no corrosive gases characteristics. According to this; these cables are used in schools, hospitals, shopping malls, airports, factories, public buildings and hotels where are crowded.
ConductorAccording to IEC, BS, EN 60228 and VDE 0295 standards; 
Class 1, Electrolytic Annealed Solid Copper Wire
InsulationAccording to EN 50290-2-26, HD 624.6 S1 and VDE 0207 standards; HI2, HFFR
SeperatorPolyester Tape
Drain WireTinned Copper Wire
Screen AL-PES Foil (100% Coverage)
Outer SheathAccording to EN 50290-2-26, HD 624.6 S1 and VDE 0207
standards; HM2, HFFR
Outer Sheath Color CodeGrey, RAL 7032
Reference StandardsVDE 0815
Flame TestEN, IEC, BS and DIN 60332-1-2 (VDE 0482-332-1-2)
Technical Characteristics
Insulation Resistance>100 M.Ωxkm
Capacitance120 nF/km 
Loop Resistance73.2 Ω/km
Operating Voltage300 V
Test Voltage800 V
Operating Temperature RangeFixed; -30 °C … +70 °C
Minumun Bending RadiusFixed; 7xD
Nominal Cross-SectionOverall Diameter (Approx.)Net Weight (Approx.)Standard Delivery Length
n x mm²mmkg/kmm
2x2x0.86.055100/500/1000
4x2x0.88.993100/500/1000
8x2x0.811.6160100/500/1000
16x2x0.815.3290100/500/1000
20x2x0.816.9428100/500/1000
32x2x0.821.1629100/500/1000
40x2x0.823.2739100/500/1000
80x2x0.831.61432100/500/1000